When i plug-in a conventional heating pad or a hair dryer into any kind of bedroom duplex, the lamp dim; and/or trips the circuit breaker. The house is of brand-new construction-- inserted in company 31 Dec 2013. My question is: have the right to I safely change the present 15 AMP Breaker v that that a 20 AMP? . . . The company cable is that 14 Gauge Copper Conductor.


*

*

No!

The only safe means to rise the circuit"s volume is by replacing the cable with among adequate gauge. For 20 amps, 12 AWG copper is adequate for up to about 100 feet.

You are watching: Change 15 amp breaker to 20 amp

If you simply replace the breaker, the wire can overheat and also ignite the structure from inside the walls.

To settle the dimming issue, inspect that the outlet is in an excellent condition and that the wires space securely fastened and not showing any kind of signs of overheating: blackening or loss of the copper shininess. Also, inspect the finish of the wire within the organization panel, both neutral and "hot" (black) wire. If those space okay, collection the appliances come a reduced wattage setting or replace them with reduced wattage models.


re-publishing
boost this answer
monitor
edited Dec 20 "13 at 20:23
reply Dec 11 "13 in ~ 0:14
*

wallykwallyk
12k11 gold badge2020 silver- badges4949 bronze badges
1
add a comment |
4
Absolutely NOT.

National Fire Protection company (NFPA) traditional Number 70, National electric Code (NEC), embraced by many states (exceptions space Missouri, Mississippi and also Arizona), requires the branch circuit Over current Protection device (OCPD --typically a circuit breaker (CB) nowadays, quite than a fuse native days of yore) to safeguard the cable/wiring hidden in your wall surfaces from overheating by de-energizing (shut off/open circuit) all outlets (lighting & receptacles) for the circuit by tripping/blowing.

Lights dimming and also CBs popping is a sure sign your residence was not developed to handle heating blankets and also hair dryers in the bedroom. Swapping the end a 20 amp breaker for the 15 amp breaker will certainly violate NEC 210.19(A)(1) and provide cause for your insurance agency not to reimburse your losses from fire & exhilaration damage and the water damage from the fire department flooding your house.

Wire is made smaller sized when produced by drawing/stretching it. The an ext times its stretched the smaller it gets. This is why American cable Gauge (AWG) appears backwards, i.e. 14AWG has actually a smaller sized diameter than 10AWG due to the fact that it was stretched more.

15 amp rated circuit breakers usage 14 AWG present carrying conductors (black hot & white neutral) + a eco-friendly ground cable which generally carries no current in sector standard outer white non-metallic sheathed cable dubbed NM-B 90 level Centigrade rated "Romex".

20 amp rated circuit breakers use the same configuration however 12 AWG, which is a bigger diameter wire 보다 14 AWG, and therefor has actually less resistance because that the exact same distance/footage native the fill center/panelboard circuit breakers. 12 AWG NM-B sheathing is fancy yellow.

10 AWG through orange sheathing would certainly be even much better electrically, but an ext expensive and also not required by "code", the NEC.

Blame every this mumbo jumbo on Physics and a German called Georg Simon Ohm who created a regulation that even Donald J. Trumped can"t repeal. Voltage loss (V) = current (i amps) time resistance (r ohms). And also Power ns = existing squared (i come the twoth power) times resistance (R).

When you attract too much current through a thin wire, since its no a superconductor, you"re converting electrical energy right into heat energy from Ohm"s resistive loss, leading to less electrical energy (a voltage drop) getting to your pack (appliance, irradiate bulb, stereo, ...). The excess heat in the wire and inside your wall surface causes the insulation to fail end time, producing a potential quick circuit attach by sparks the ignite flammables.

Have a licensed and insured electrician (Journeyman or Master) or electrical contractor add a brand-new 20 amp circuit, or change the currently 14 AWG cabling through 12 AWG cabling, or use your hair dryer in the bathroom i beg your pardon should currently have a GFCI every NEC 210.8(A)1) and 20 amp receptacle per NEC 210.11(C)3) set up within three feet of the sheet of a container per NEC short article 200, section III required Outlets, 210.52 dwelling Unit Receptacle Outlets, (D) Bathroom.